SAFETY AND PROTECTION IN THE MANAGEMENT OF
ELECTRIC DISTRIBUTION LV-MV-HV

MV – Electronic capcitive unipolar MV voltage detector – without contact

Voltage range: see tab. A and B
Frequency: 50÷60 Hz
Signalings: optic and acoustic
Automatic self check: cyclic every 3 seconds
Shut-down: automatic timed or by subsequent press of the power button
Power supply: 1 battery 9 V
Insulating stick L= 0,6 m with handle
Connection: universal fixing adaptor
Case: rigid nylon bag with shoulder belt
MV – Electronic capcitive unipolar MV voltage detector – without contact
Download technical sheet

Our Mod. RMT-CARR.

TAB. B

Safety distance

Voltage (kVac) Min. safety distance suggested (mm) Min. safety distance to keep (mm)
<1 300 (don’t touch with hands or body)
3 1120 60
12 1155 140
33 1350 350
 

TAB. A

Typical detection distance

Voltage phase to earth (kVac) Typical detection distance from line or part to check (mm)
0,23 10
3 1200
12 3000
33 4000