TAB. B
Safety distance
Voltage (kVac) | Min. safety distance suggested (mm) | Min. safety distance to keep (mm) |
---|---|---|
<1 | 300 | (don’t touch with hands or body) |
3 | 1120 | 60 |
12 | 1155 | 140 |
33 | 1350 | 350 |
SAFETY AND PROTECTION IN THE MANAGEMENT OF
ELECTRIC DISTRIBUTION LV-MV-HV
Voltage range: see tab. A and B |
Frequency: 50÷60 Hz |
Signalings: optic and acoustic |
Automatic self check: cyclic every 3 seconds |
Shut-down: automatic timed or by subsequent press of the power button |
Power supply: 1 battery 9 V |
Insulating stick L= 0,6 m with handle |
Connection: universal fixing adaptor |
Case: rigid nylon bag with shoulder belt |
Our Mod. RMT-CARR.
Safety distance
Voltage (kVac) | Min. safety distance suggested (mm) | Min. safety distance to keep (mm) |
---|---|---|
<1 | 300 | (don’t touch with hands or body) |
3 | 1120 | 60 |
12 | 1155 | 140 |
33 | 1350 | 350 |
Typical detection distance
Voltage phase to earth (kVac) | Typical detection distance from line or part to check (mm) |
---|---|
0,23 | 10 |
3 | 1200 |
12 | 3000 |
33 | 4000 |