Voltage range: 50÷380 kV |
Frequency: 50÷60 Hz |
Signalings: optic and acoustic |
Automatic self check: cyclic every 3 seconds |
Shut-down: automatic timed or by subsequent press of the power button |
Power supply: n° 1 battery 9 V |
Connection: adaptor0 |
Insulating stick L= 0,56 m adjustable head 0-45-90° |
Case: rigid nylon bag with shoulder belt |
SAFETY AND PROTECTION IN THE MANAGEMENT OF
ELECTRIC DISTRIBUTION LV-MV-HV
HV – Electronic capacitive unipolar HV voltage detector – non contact with electric field detection 50÷380 kV – HV lines
OPERATION ON HV OVERHEAD LINES
The test of voltage absence is done using RCE LA detector, holding the detector from the handle and using it near the active parts in accordance to safety distance as shown on Tab. 1 and on Fig. 2, 3 and 4. |
MINIMUM SAFETY DISTANCE
The minimum safety distance between the live part and the part closest to the operator’s body, if not protected from metallic structure, has to be at least as shown in Tab. 1. Specific method of work must be defined for the right use of this detector |

Download technical sheet
Ref. STF RSXP 002 TERNA
Our Mod. RCE LA
VOLTAGE KV | MINIMUM SAFETY DISTANCE (mm) |
---|---|
132 | 1520 |
150 | 1670 |
220 | 2300 |
380 | 3940 |