SAFETY AND PROTECTION IN THE MANAGEMENT OF THE RAILWAY TRACTION
RAYLWAYS| SUBWAYS| TRAMWAYS | TROLLEY-BUS
Earthing and short circuit mobile device for contact lines 3 kVdc with three elements for crane trailers and rescue trailers
COMPOSITION:
No. 1 light alloy contact clamp with foldable jaw and screw tightening provided with aluminum torque limiter bound to the active part, length 1,53 m |
No. 2 insulating sticks in epoxy resin, base plus extension, each with length 1,53 m, joinable through press button joint. The base is provided with hand protection and end cap with strengthened joint for the connection to the aluminum pipe. |
Total length of the device 4,6 m. |
No. 1 copper flexible cable, sec. 95 mm2 length = 5,51 m covered with silicone sheath. |
No. 1 clamp for the connection to the rail provided with torque limiter for the tightening of the clamp on the rail. |
Optional: – Nylon bag with shoulder belt for the transfer. |

Download technical sheet
In accordance to STD IEC 61230
Ref./Conf. STF RFI DMA IM TE SP IFS 083 – Cat. 817/602
Our Mod. CCLC-SDN/95/3 – 5,5 m
Cable sec. mm2 | Icc 0,25s | Icc 0,5s | Icc 1s |
---|---|---|---|
95 | 40 kA | 35 kA | 25,2 kA |