SAFETY AND PROTECTION IN THE MANAGEMENT OF THE RAILWAY TRACTION
RAYLWAYS| SUBWAYS| TRAMWAYS | TROLLEY-BUS
Earthing and short circuit mobile device for contact lines 25 kVac – 50 Hz two elements
COMPOSITION:
No. 1 light alloy contact clamp with foldable jaw and screw tightening provided with aluminum torque limiter bound to the active part, length 2,1 m |
No. 1 insulating sticks in epoxy resin, base plus extension, each with length 2,35 m provided with hand protection and end cap with strengthened joint for the connection to the aluminum pipe. |
Total length of the device 4,6 m. |
No. 1 copper flexible cable, sec. 50 mm2 length = 6,1 m covered with silicone sheath. |
No. 1 clamp for the connection to the rail provided with torque limiter for the tightening of the clamp on the rail. |
Optional: – Nylon bag with shoulder belt. |

Download technical sheet
In accordance to STD IEC 61230
Ref./Conf. STF RFI DMA IM TE SP IFS 003 – Cat. 817/603
Our Mod. CCLC-SDN/50/2-6,1 m – LN
Sez. cavo mm2 | Icc 0,25s | Icc 0,5s | Icc 1s |
---|---|---|---|
50 | 22,5 kA | 18 kA | 12,7 kA |