Earthing and short circuit mobile device for contact lines 25 kVac – 50 Hz two elements

COMPOSITION:

No. 1 light alloy contact clamp with foldable jaw and screw tightening provided with aluminum torque limiter bound to the active part, length 2,1 m
No. 1 insulating sticks in epoxy resin, base plus extension, each with length 2,35 m provided with hand protection and end cap with strengthened joint for the connection to the aluminum pipe.
Total length of the device 4,6 m.
No. 1 copper flexible cable, sec. 50 mm2 length = 6,1 m covered with silicone sheath.
No. 1 clamp for the connection to the rail provided with torque limiter for the tightening of the clamp on the rail.
Optional:
– Nylon bag with shoulder belt.
Earthing and short circuit mobile device for contact lines 25 kVac – 50 Hz two elements
Download technical sheet

In accordance to STD IEC 61230
Ref./Conf. STF RFI DMA IM TE SP IFS 003 – Cat. 817/603
Our Mod. CCLC-SDN/50/2-6,1 m – LN

Sez. cavo mm2 Icc 0,25s Icc 0,5s Icc 1s
50 22,5 kA 18 kA 12,7 kA