SAFETY AND PROTECTION IN THE MANAGEMENT OF
ELECTRIC DISTRIBUTION LV-MV-HV
Earthing and short circuit equipment for MV systems on bare conductors of MV substations
cod. 11002158PR
Pos.
A42
A42
LELE05
COMPOSITION:
n° 3 light alloy adjustable clamps with screw tightening CH22 at hexagonal shenk: – ø 3÷18 mm on cylindrical conductors – thickness max 60×12 mm on flat bars |
n° 3 copper cables sec. 25/35 mm2 L=1 m covered with silicone sheath |
n° 1 three-ways insulated connector |
n° 1 copper cable sec. 16 mm2 L=2 m covered with silicone sheath |
n° 1 earthing aluminium alloy clamp thickness 0÷40 mm |
n° 1 telescopic insulating stick L=1/1,5 m or in 2 elements of 0,75 m each (with simplex joints) |
n° 1 metal box |
Optional: – n° 1 voltage detector 4-30 kV |

Download technical sheet
In accordance to STD IEC 61230 and IEC 50110-1
Ref. STF EA0320 ENEL DISTRIB.
Our Mod. MT 100 ± VOLT. DETECT.
Cable sec. mm2 | Icc 0,25s | Icc 0,5s | Icc 1s |
---|---|---|---|
25 | 13,7 kA | 8 kA | 5,6 kA |
35 | 15,7 kA | 11,1 kA | 8 kA |