SAFETY AND PROTECTION IN THE MANAGEMENT OF
ELECTRIC DISTRIBUTION LV-MV-HV
Earthing and short circuit equipment for MV systems on bare conductors of LV/MV substations – cylindrical conductors
Composition:
n° 3 light alloy clamps with spring tightening ø 3÷20 mm |
n° 1 light alloy clamp holder head, complete of recover hook |
n° 2 copper cables sec. 25 mm2 L=2 m covered with silicone sheath |
n° 1 earthing copper cable sec. 16 mm2 L=6 m covered with silicone sheath |
n° 1 earthing self-milling light alloy clamp with screw tightening 0÷40 mm |
n° 1 voltage detector 4÷30 kV |
n° 1 insulating stick L=3 m on 2 elements with nylon bag |
n°1 metal box |

Download technical sheet
In accordance to STD IEC 61230 and IEC 50110-1
Ref. STF EA 0320/17 ENEL DISTRIB.
Our Mod.BMT 18 EA 0320-17
Cable sec. mm2 | Icc 0,25s | Icc 0,5s | Icc 1s |
---|---|---|---|
25 | 13,7 kA | 8 kA | 5,6 kA |
35 | 15,7 kA | 11,1 kA | 8 kA |