Ottotecnica
Italiano
English
Distribution

SAFETY AND PROTECTION IN THE MANAGEMENT OF
ELECTRIC DISTRIBUTION LV-MV-HV

Earthing and short circuit equipment for HV substations on cylindrical conductors

Composition:

n° 3 light alloy clamps with screw tightening on cylindrical conductors ø 5÷70 mm – ø 5÷105 mm – ø 5÷130 mm available with DIN/BAYONET/HEXAGON CH25 heads
n° 3 copper cables sec. 50/70/95 mm2 L=6/9/12 m covered with silicone sheath
n° 3 earthing brass clamps thickness 0÷35 mm and spherical fixed points ø 20/25 mm
n° 1 insulating stick L=4÷6 m in 2 or 3 elements with alloy joints
n° 1 nylon bag
n° 1 metal box
Earthing and short circuit equipment for HV substations on cylindrical conductors
Download technical sheet

In accordance to STD IEC 61230
Ref. STF EA 0480 ENEL DISTRIB.
Our Mod.ATL 70/105/130 – D/B/E

Cable sec. mm2 Icc 0,5s Icc 1s
50 18 kA 12,7 kA
70 26 kA 18,6 kA
95 35 kA 25,2 kA