Earthing and short circuit device for MT plants in bare conductors of railway substations – DC side
COMPOSITION:
No. 1 light allow clamp with threaded coupling DIN, bayonet or hexagon CH 25 and tightening: – ø 14÷70 mm on cylindrical conductors – Thickness. 20÷110 mm on flat bar – Thickness. 50÷120 mm with inclined closure – on spherical fixed points, diameter ø 25 mm |
No. 1 copper cable sec. 50/70/95 mm2 length = 1÷5 m covered with silicone sheath |
No. 1 earthing brass clamp with screw tightening thickness 0÷50 mm and spherical fixed points |
No. 1 insulating stick, length = 4÷6 m in two or three joinable elements with aluminum joints and stop ring |
No. 1 nylon bag with shoulder belt for the stick |
No. 1 metal box |

Download technical sheet
In accordance to STD IEC 61230
Ref./Conf. STF RFI DPRIM STF SS 020
Our Mod. ATL 110 – D/B/E
Cable sec. mm2 | Icc 0,5s | Icc 1s |
---|---|---|
50 | 18 kA | 12,7 kA |
70 | 26 kA | 18,6 kA |
95 | 35 kA | 25,2 kA |