In compliance with the STD IEC 61230 e EN 50110-1
Ref./Conf. TERNA
Our Model C.TO C.TO BATT.COND/TERNA
SAFETY AND PROTECTION IN THE MANAGEMENT OF
ELECTRIC DISTRIBUTION LV-MV-HV
Earth and short circuit device for the primary batteries of HV/MV capacitors – quadropole configurations
Composition:
n° 4 aluminum alloy clamps with tightening through hexagonal tail CH 12 on: – Cylindrical conductors ø 5÷ø 40 mm – Flat bars max thickness 60×50 mm – Inclined bars with max thickness 35 mm – Side bars max thickness 25×60 mm – Spherical fixed points ø 20 e ø 25 |
n° 3 copper cables section 25/35/50 mm2 length = 1m covered with transparent silicone sheath |
n° 1 copper earth cable section 16/25/35/50 mm2 length =5m covered with transparent silicone sheath |
n° 1 self-milling earth clamp in aluminum alloy with screw tightening on conductors with max thickness 40 mm |
n° 1 insulating stick in fiberglass length=1,5 m in two joinable parts with simplex joint. Working hexagon head CH12: hand-guard and end rubber stopper. |
n° 1 painted steel sheet container for the storage and the transfer of the device. |
On demand: – n° 1 voltage detector MV 4÷30 kV with optical/acoustic signal. Battery supply 9V. Fork shaped electrode and hexagon CH12 coupling. |

Download technical sheet
Cable sec. mm2 | Icc 0,25s | Icc 0,5s | Icc 1s |
---|---|---|---|
25 | 13,7 kA | 8 kA | 5,6 kA |
35 | 15,7 kA | 11,1 kA | 8 kA |
50 | 22,5 kA | 15,9 kA | 12,7 kA |