Extra-flexible copper cables covered by silicon sheath

Extra-flexible copper cables covered by silicon sheath
Download technical sheet

In accordance to IEC 61138, IEC 60228

Note: values of short-circuit are calculated in reference to a maximum temperature rise of ~ 300 ° C.

SECTION mm2 Ø ELEMENTARY WIRE A max B max Ω/Km Kg/m Icc 0,5S Icc 1S
16 ≤0,21 9,5 mm 6,4 mm 1,210 0,17 5,1 KA 3,6 kA
25 ≤0,21 11,2 mm 8 mm 0,780 0,26 11,3 KA 5,6 kA
35 ≤0,21 12,7 mm 9 mm 0,554 0,36 15,7 KA 7,9 kA
50 ≤0,21 15,2 mm 13 mm 0,386 0,52 22,5 KA 11,2 kA
70 ≤0,21 17,4 mm 15 mm 0,272 0,71 31,5 KA 15,7 kA
95 ≤0,21 19,9 mm 16 mm 0,206 0,99 42,8 KA 21,4 kA
120 ≤0,21 22 mm 18 mm 0,161 1,18 54 KA 27 kA