Ottotecnica
Mondo
ENGLISH
Select language
Distribution

Earthing and short circuit devices, voltage detectors and phase comparators, sectioning and operation insulating sticks, insulating materials and individual protective equipment

SAFETY AND PROTECTION IN THE MANAGEMENT OF
ELECTRIC DISTRIBUTION LV-MV-HV

Earthing and short circuit equipment for MV systems on bare conductors of LV/MV substations – cylindrical conductors

Composition:

n° 3 light alloy clamps with spring tightening ø 3÷20 mm
n° 1 light alloy clamp holder head, complete of recover hook
n° 2 copper cables sec. 25 mm2 L=2 m covered with silicone sheath
n° 1 earthing copper cable sec. 16 mm2 L=6 m covered with silicone sheath
n° 1 earthing self-milling light alloy clamp with screw tightening 0÷40 mm
n° 1 voltage detector 4÷30 kV
n° 1 insulating stick L=3 m on 2 elements with nylon bag
n°1 metal box
Earthing and short circuit equipment for MV systems on bare conductors of LV/MV substations – cylindrical conductors
Download technical sheet

In accordance to STD IEC 61230 and IEC 50110-1 
Ref. STF EA 0320/17 ENEL DISTRIB. 
Our Mod.BMT 18 EA 0320-17

Cable sec. mm2 Icc 0,25s Icc 0,5s Icc 1s
25 13,7 kA 8 kA 5,6 kA
35 15,7 kA 11,1 kA 8 kA